KM – FD2000 is a fire proofing ventilation grille to preserve the air inlet and outlet area in compartment structures or as an alternative to a fire fighting air lock in conditioned air plants.
DESCRIPTION The KM – FD2000 grille is made up of a calcium silicate frame, the fins are covered on both sides with KM-FF107 thermo-expandable strips. FUNCTIONALITY The grille is put in the hole of the wall or the door and fixed with fireproofing KM SEALER F putty. The grille can also be inserted into the air duct as an alternative to a fire fighting air lock. In case of fire or hot smokes, the intumescent strips expand and seal the grille. CERTIFICATIONS • According to European Standard UNI-EN 1366-3 EI 60/E90 on plasterboard walls. FEATURES KM-FD2000 is a fire fighting grille to protect the ventilation windows in walls, doors or ducts and in replacement of fire-fighting airlocks. The frame is made up of calcium silicate. The grills are covered with graphitic intumescent strips KM-FF107. APPLICATION The grille can be inserted inside the duct and fixed with self-tapping screws or KM SEALER F fire-proofing putty. Any gaps between grille and the support element can be sealed with silicone-based fire-proofing putty KM SEALER F. Square grilles are put in circular section ducts and the empty area of the circular cross-section is sealed with graphitic intumescent sponge KM-FF108, sealed with silicone fire-proofing KM SEALER F putty.
Dimensions: on request axb Thickness: 60 mm Reaction temperature: 150°C Toxic fumes emission: none Storage: not exposed to bad weather Transport: no restrictions on land no restrictions ICAO/IATA-DGR
FURTHER INFORMATION It does not require any precautionary measures for its use and handling. Classification and labeling: the material does not require any special labeling. Danger symbols and indications: none. Warnings: none. Safety advice: none.