EMPLOYMENT FIELDS The KM-FF 108 gasket is used for sealing the gap between the structural element and cable ducts, electrical cable bundles, metal pipes, insulated metal pipes, combustible pipes, copper pipes, insulated copper pipes, fire dampers and for sealing structural joints. Some sealing systems involve the application of the KM-FF 108 gasket with the KM BOARD V1 panel, KM-SEALER F putty, KM-FC 120/180 COVER coating.
MODALITY OF USE cut the KM-FF seal 108 to size with a cutter-type blade and insert it inside the empty space of the through hole. Subsequently, seal the exposed surface of the gasket and any leaks between the gasket and the structural element with KM SEALER F stucco. The sealing must be performed on both sides of the wall and on the lower side of the floor.
CERTIFICATIONS • According to the European Standard UNI-EN 1366-3 • According to the European Standard UNI-EN 1366-4
TECHNICAL DATA • Color: dark gray • Density:225 kg/mc • Free expansion: 2 times at 450ºC in 15 min • Pressure: 5 bar at 400 ºC • Flash point: non-flammable • Reaction temperature: 250°C • Compressibility: up to 50% • Dangerous reactions: none observed • Storage: in a closed environment not exposed to water and humidity • Transportation: No ground restrictions, no ICAO/IATA-DGR restrictions (not in direct contact with edible products)
FURTHER INFORMATION • Precautionary measures: does not require any precautionary measures for either use or handling. • Acute effects on exposure: none • Classification and labelling: the material does not require any particular labelling • Risk phrases: none • Cautionary advice: none