KM IMPIANTI

FIRE RESISTANT COATING

Code:
KM-FC 120 COVER
KM-FC 180 COVER
The KM-FC 120/180 COVER is made up of a 400 gr/m2 high-temperature outer fabric, raw on one side and aluminized on the other. The compound consists of a double layer of eco-friendly biosoluble felt for high temperatures of 128 kg/mc, a sheet of ceramic paper, all re-edged with a reinforced Kevlar wire

CONTACT US

CONTACT US

PRODUCT SHEET

FORMAT
Rolls 5000 x 1200 mm, thickness 30 mm.

EMPLOYMENT FIELDS
The KM-FC 120 COVER coating is used for fire protection air ducts.
The KM-FC180 COVER coating is used for fire protection of copper pipes for biomedical gases, cable ducts and fire dampers.

MODALITY OF USE
Line the system to be protected with KM FC 120/180 COVER and secure it with metal wire.
Each longitudinal section of cladding must be overlapped by 50/150 mm. The perimeter overlap shall be approximately 100/600 mm in proportion to the development of the cladding. The joints should be protected with adhesiveized aluminum tape KM-ALU TAPE. At each overlap the liner is further secured with KM-CGH fabric sealing straps.

CERTIFICATIONS
• KM-FC120COVER According to the European Standard UNI EN 1366-1 (OUTDOOR FIRE)*
• KM-FC180COVER According to the European Standard UNI EN 1366-3
According to the European Standard UNI EN 1366-5 (EXTERNAL FIRE)

* FIRE-RESISTANT COATINGS FOR RECTANGULAR AND CIRCULAR AIR DUCTS:
• EI120 According to the European Standard UNI EN 1366-1 (INTERNAL FIRE)
• EI120 According to the European Standard UNI EN 1366-8 (FUME EXTRACTION)
European Technical Assessment (ETA) Certification 18/0691 AND 18/0690
CONTACT US
TECHNICAL DATA
• Outer covering: white colour raw fibre fabric/400 gr/m2 aluminised fibre fabric.
• Internal material: 128 kg/mc eco-friendly biosoluble fiber felt, 1 mm ceramic paper
• Usage temperature: up to 550°/600°C
• Weight: 5 kg/m2.
• Thickness: nominal 30 mm ± 5%
• Storage: in a closed environment not exposed to water and humidity
• Transportation: No ground restrictions, no ICAO/IATA-DGR restrictions
(not in direct contact with edible products)

FURTHER INFORMATION
• Precautionary measures: Does not require any precautionary measures for both use and handling
• Acute effects on exposure: none
• Classification/labeling: the material does not require any particular labeling
• Risk phrases: none
• Prudence advice: none
Data Sheet
KM IMPIANTI SRL
Via Meucci 26/28, 20060 Gessate
Milano - Italy
p.iva 10901020155
Tel: +39 0295350051
Realizzato da 
key4web
linkedin facebook pinterest youtube rss twitter instagram facebook-blank rss-blank linkedin-blank pinterest youtube twitter instagram