KM IMPIANTI

PRESSURIZATION SYSTEMS FOR SMOKEPROOF FILTERS

Code:
KM-QSLAVE-PLCMICRO
KM-QSLAVE-SF
The KM-QSLAVE PLC MICRO/KM-QSLAVE SF system is designed to create overpressure to protect the smoke filter areas. It is made up of several components divided into 4 units:
• A. command and management unit.
• B. buffer accumulator panel.
• C. presurizer (electric fan) with Brushless motor.
• D. differential pressure gauge.
 

CONTACT US

CONTACT US

PRODUCT SHEET

INFORMATION DATA
The KM-QSLAVE PLC MICRO/KM-QSLAVE SF smoke filter system is used when there is a need to manage fire risk, safeguarding the areas defined by the project “safe”. These areas require interventions with complementary systems aimed at preventing the fire and fumes resulting from this risk from invading the so-called safe areas or smoke-proof filter zones from other areas. By designing compartmentalization walls and slabs, access fire doors, and any fire-resistant seals for plant crossings, which characterize fire- and smoke-proof areas, it is important to ensure that the areas themselves are kept under pressure towards the risk zones, so as to prevent the opening of fire doors from endangering the filter zone.

INSTALLATION
Command unit A is attached to unit B, the buffer battery box, and must be placed in the filter area or in any case in a safe area. Unit D, differential pressure gauge, shall be placed in the safe zone at a distance from the control panel not exceeding 6 ml of cord. The distance from the picture should not exceed 9 ml of cord. Unit C, pressurisation electric fan, shall be placed with the front ejection face in the safe zone to be pressurised, either wall or slab.

CERTIFICATIONS
• PRESSURIZATION SYSTEM
Test certificates from the Giordano Institute for Pressurization Systems for Smoke-Proof Filters in accordance with the Ministerial Decree of 30/11/1983 (mod. SF and PLC) and compliant with the European standard UNI EN12101-6:2005 (mod. PLC).

• AIR TRANSPORT PIPELINE
Protection with fire-resistant coating KM-FC120COVER with APPLUS Certificate according to the European standard UNI EN1366-1.

• TYPOLOGIES
- KM-QSLAVE PLC MICRO/PLC MICRO 2 (single/double pressurizer).
- KM-QSLAVE PLC MICRO 6 (up to 6 pressurizers).
- KM-QSLAVE PL/PL2 (QSLAVE-PLC MICRO management framework).
- KM-QSLAVE SF (single pressurizer).
- KM-QSLAVE SF2 (dual pressurizer).
- KM-QSLAVE SF opt (with timer).
- KM-QSLAVE SF2 opt (with timer).
CONTACT US
TECHNICAL DATA
UNITA' A:
• power supply with 220V-50Hz/24V transformer.
• emergency power supply with 2 FIAMM FG24204 buffer accumulators.
• management of standby or continuous 24h operation.
• manual system activation button.
• led status viewer.
• on-board panel protection.
• key lock of the painting.
• square size 400x400x250 mm, left hinge hatch.
• IP20 protection.
• weight 16 kg.

- KM-QSLAVE SF BASE MODEL
• potentiometer for regulating overpressure.
• double presurizer control.
• timer (on request) for filter rooms or with normally open doors.

- KM-QSLAVE PLC MODEL
• on-board control software.
• self-regulation of overpressure.
• programmable period self-test.
• self-management of the Overpressure Test 120’.
• definition of overpressure.
• maximum overpressure regulation.
• maximum increase in overpressure with self-regulation.
• PLC management of standby or continuous 24h operation.
• system configuration and management with 3-level security psw.
• internal expansion modules (on request).
• extra management up to 6 pressurizers and 2 expansion panels (on request).
• integrated timer.
• PLC display with programming and command display.
• downloadable reports: correct installation and activation System.
• scheduled periodic self-test.
• overpressure test.
• historic alarms.
Standby operation of the system presupposes activation by connection with a centralised or localised fire/smoke detection system and with a manual push-button alarm system.

UNITA’ B:
• buffer accumulator panel.
• 2 FIAMM mod buffer batteries. FGC24204 12V, 42Ah (Annual Replacement).
• dimensions 250x400x250 mm.
• IP20 protection.
• weight 34 kg.
• rear wall mounting brackets (equipped).

UNITA’ C:
• pressurizer with crankcase, nominal flow rate 3000 m³/h.
• Brushless 24V cc axial electric fan, 48,000 h (approx. 5 years) continuous functionality.
• 315 mm (male) duct connection.
• flat protective grille, painted RAL9005.
• front air expulsion.
• dimensions 400x400x80 mm.

UNITA’ D:
• Differential Pressure Gauge (MDP).
• Power supply from 24V DC control panel.
• Digital display in Pascal.
• PVC spout (external filter for differential measurement with safe zone).
• 2 ml of crystal tube.
Data Sheet
KM IMPIANTI SRL
Via Meucci 26/28, 20060 Gessate
Milano - Italy
p.iva 10901020155
Tel: +39 0295350051
Realizzato da 
key4web
linkedin facebook pinterest youtube rss twitter instagram facebook-blank rss-blank linkedin-blank pinterest youtube twitter instagram